Level Transmitter Configuration & Horizontal and Vertical Vessel Volume Calculator

LTconfig is an offline, mobile-first field tool for instrument technicians, commissioning engineers, and operators. Use it to convert between %span, mA, and height of liquid in a horizontal or vertical vessel. It calculates horizontal and vertical vessel (tank) volume. It sets the 4–20 mA level transmitter scaling (LRV, URV, measuring span) for any 4–20 mA transmitter: differential pressure (DP), displacer, capacitance, or guided wave radar (GWR). For GWR on a bridle or chamber, it does more. From your nozzle elevations, flange face, and probe length, it calculates the null (blanking) zones, the AMS tank height, and the LRV/URV span. It runs fully in your browser and works with no signal in the field.

Jump to: vessel volume · transmitter span · GWR bridle · FAQ

Horizontal and vertical vessel (tank) volume

The partial volume of a horizontal cylinder is the circular-segment area at the liquid level, multiplied by the shell length. Add the volume of the two heads (2:1 ellipsoidal, hemispherical, or ASME 80:10 F&D torispherical). Flat heads add no volume. Segment area: A = R²·acos((R−h)/R) − (R−h)·√(2Rh−h²), where R is the inside radius and h is the level. Worked example: 60″ ID × 20 ft shell, 2:1 ellipsoidal heads, liquid at 36″ → ≈ 1,999 gal (47.6 bbl). The output is in gallons or barrels.

For a vertical vessel, add the liquid in the bottom head, the cylindrical shell (πR² multiplied by the liquid height in the shell), and the top head. Datum 0 is the bottom seam, so the bottom head is below 0. Worked example: 48″ ID × 10 ft seam-to-seam, 2″ straight flange, 2:1 ellipsoidal heads, liquid 60″ above the bottom seam → ≈ 548 gal (13.1 bbl).

Level transmitter span (LRV / URV)

LRV is the level at 4 mA (0%). URV is the level at 20 mA (100%). The measuring span is URV − LRV. These values apply to any 4–20 mA level transmitter: differential pressure (DP), displacer, capacitance, or guided wave radar. The loop current is mA = 4 + 16·(level − LRV) / (URV − LRV). Worked example: LRV 10″, URV 90″, level 50″ → 12 mA (50% of span). The tool accepts a suppressed or elevated zero. It also makes a setpoint table (also called a strapping table) of the level and mA at each alarm setpoint.

Guided wave radar (GWR) bridle & chamber: null zones & LRV/URV span

Enter the upper and lower process nozzle elevations, the flange face (upper reference), and your probe length. LTconfig calculates the upper and lower null (blanking) zones and the AMS tank height. It sets LRV at the lower nozzle (or higher, if the probe blind zone reaches above it) and URV at the upper nozzle, in the limits of the vessel. This gives the measuring span. With a middle nozzle, it also gives the interface level span. A sight-glass reading cross-checks the LT reading, in inches. Worked example: lower nozzle 12″, upper nozzle 84″, flange face 88″, probe length 79″ → upper null 4″, lower null 3″, LRV 12″, URV 84″, span 72″.

FAQ

How do you calculate the volume of a horizontal vessel?
The partial volume of a horizontal cylinder is the circular-segment area at the liquid level, multiplied by the shell length. Add the volume of the two heads (2:1 ellipsoidal, hemispherical, or ASME 80:10 F&D torispherical). Flat heads add no volume. The segment area is A = R²·acos((R−h)/R) − (R−h)·√(2Rh−h²). LTconfig calculates the volume from the inside diameter, shell length, head type, and level.

How do you calculate the volume of a vertical vessel?
Add three parts: the liquid in the bottom head, the liquid in the cylindrical shell (πR² multiplied by the liquid height in the shell), and the liquid in the top head if the level reaches it. LTconfig measures the level from the bottom seam (datum 0), so the bottom head is below 0. Enter the height seam-to-seam, or tangent-to-tangent with the straight flange of the head.

How do you set LRV and URV for a level transmitter?
LRV is the level at 4 mA (0%). URV is the level at 20 mA (100%). The measuring span is URV minus LRV. The loop current is mA = 4 + 16·(level − LRV) / (URV − LRV). Enter the range. LTconfig then gives the span and the expected mA at each level. You set these range values when you calibrate or range the transmitter. LTconfig calculates the values to enter. It does not make the as-found/as-left calibration record.

How do you configure guided wave radar (GWR) on a bridle?
Enter the upper and lower nozzle elevations, the flange face (upper reference), and your probe length. LTconfig calculates the upper and lower null (blanking) zones and the AMS tank height. It sets LRV at the lower nozzle (or higher, if the probe blind zone reaches above it) and URV at the upper nozzle, in the limits of the vessel. This gives the measuring span.

How do you find the null zones and LRV/URV span for a GWR bridle?
Use the bridle geometry. Enter the upper and lower nozzle elevations, the flange face (upper reference), and your probe length. LTconfig gives the upper and lower null (transition and end blanking) zones, the AMS tank height, and the measuring span. LRV is at the lower nozzle (or higher, if the probe blind zone reaches above it) and URV is at the upper nozzle, in the limits of the vessel. This is a field commissioning reference, not a calibrated record.

How do you replace a displacer with guided wave radar (GWR) in a chamber?
Use the existing displacer chamber and bridle taps again. Set LRV at the lower nozzle (or higher, if the probe blind zone reaches above it) and URV at the upper nozzle, in the limits of the vessel. Enter the nozzle elevations, the flange face, and your GWR probe length. LTconfig then gives the upper and lower null (blanking) zones and the LRV/URV span for the retrofit.

What is the difference between LRV and URV?
LRV (Lower Range Value) is the process level at which the transmitter output is 4 mA / 0%. URV (Upper Range Value) is the level at which the output is 20 mA / 100%. The difference, URV minus LRV, is the measuring span.

What is a strapping table?
In custody transfer, a strapping table shows tank volume against height. LTconfig makes the field equivalent: a setpoint table that you enter. It shows the level and the related mA at each alarm setpoint that you select. Use it to find the correct transmitter value at each setpoint. It comes from the LRV/URV range and your setpoints, not from a custody calibration.

What is suppressed or elevated zero?
Suppressed or elevated zero means that the 4 mA point (LRV) is not at the tap or the vessel bottom. LTconfig sets 4 mA and 20 mA at the levels that you enter. Because of this, it accepts a suppressed or elevated zero directly.

Does LTconfig work for non-GWR level transmitters?
Yes. The horizontal and vertical vessel volume and the 4–20 mA level transmitter span (LRV, URV, and measuring span) work for any 4–20 mA level transmitter: differential pressure (DP), displacer, capacitance, or guided wave radar. Only the bridle and chamber configurator is specific to GWR. It calculates the null zones and AMS tank height from probe and nozzle geometry.

LTconfig works with guided wave radar level transmitters, for example Rosemount 5300-series, AMETEK Magnetrol Eclipse, and Endress+Hauser Levelflex. LTconfig is an independent tool. No manufacturer is affiliated with it or endorses it. Product names are for compatibility reference only. Always compare the results with the manual of the transmitter.